metal mesh primary air filter

metal mesh primary air filter Application:primary filtration in the air conditioner systems especially in acids,and base resistance Frame: aluminium alloy Media:ripple shape of multilayer of alluminum alloy

INTRODUCTION:

    Application:primary filtration in the air conditioner systems
    especially in acids,and base resistance
    Frame: aluminium alloy
    Media:ripple shape of multilayer of alluminum alloy
    Efficiency:G2(EN779)<65-80%
    Design features:all-metal net filter have low loss of pressure capturing ability
    filter net is ripple net by multilayer

    Dimension(mm)

    Rate airflow
    (m3/h)

    Pressure drop
    (pa)

    EN779

    No. of the media

    Remarks

    W*H*D

    595*595*21

    4000

    ≤25

    G2

    4-5

    2floor 3*6*6 wave net
    1floor 3*6*8 wave net
    1-2 floor 3*6 flat net

    495*595*21

    3200

    ≤25

    G2

    4-5

    290*595*21

    2000

    ≤25

    G2

    4-5

    495*495*21

    2500

    ≤25

    G2

    4-5

    395*595*21

    2200

    ≤25

    G2

    4-5

    295*495*21

    1500

    ≤25

    G2

    4-5

    595*595*25

    4000

    ≤30

    G2

    5-6

    4 floor 3*6*6 wave net
    1-2 floor 3*6 flat net

    495*595*25

    3200

    ≤30

    G2

    5-6

    290*595*25

    2000

    ≤30

    G2

    5-6

    495*495*25

    2500

    ≤30

    G2

    5-6

    395*595*25

    2200

    ≤30

    G2

    5-6

    295*495*25

    1500

    ≤30

    G2

    5-6

    595*595*46

    4000

    ≤35

    G2

    6-7

    2 floor 3*6*6 wave net
    4 floor 3*6*8 wave net
    0-1 floor 3*6 flat net

    495*595*46

    3200

    ≤35

    G2

    6-7

    290*595*46

    2000

    ≤35

    G2

    6-7

    495*495*46

    2500

    ≤35

    G2

    6-7

    395*595*46

    2200

    ≤35

    G2

    6-7

    295*495*46

    1500

    ≤35

    G2

    6-7